Mitsubishi Electric 800 Series Instruction Manual (Function page 426

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
Input
Input terminal
specification
0 to 5 V
Terminal 2
0 to 10 V
0 to 20 mA
0 to 5 V
Terminal 4
0 to 10 V
0 to 20 mA
*5
Can be changed by Pr.73 Analog input selection, Pr.267 Terminal 4 input selection and the voltage/current input switch. (Refer to
NOTE
• Always calibrate the input after changing the voltage/current input specification with Pr.73 and Pr.267, and the voltage/current
input selection switch.
 PID input method according to the operation mode
• The input methods of the set point, measured value, and deviation differ depending on the operation mode as follows.
• Set point input
PID action selection
Command
source
Pr.128
Pr.609
60, 61
Communication
1000,
4
1001
1000,
5
PLC function
1001
20, 21
External
1000,
2, 3
1001
*1
CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic are available.
*2
Input value is "0" when the PLC function is disabled. PID control is disabled when bit 0 of SD1255 is "0".
*3
When Pr.133 ≠ "9999", the Pr.133 setting is used for the set point.
*4
When communication is not specified for the command source in the Network operation mode or when the speed command source is other than
communication, the set point cannot be input via communication. Instead, it can be input via an external terminal (PID control is enabled).
• Measured value input
PID action selection
Command
source
Pr.128
Pr.610
60, 61
Communication
1000,
4
1001
1000,
5
PLC function
1001
20, 21
External
1000,
2, 3
1001
*5
CC-Link, CC-Link IE TSN, and CC-Link IE Field Network Basic are available.
Relationship with analog input
*5
Set point
0 V = 0%
0 V = 0%
5 V = 100%
5 V = 100%
0 V = 0%
0 V = 0%
10 V = 100%
10 V = 100%
0 mA = 0%
0 mA = 0%
20 mA = 100%
20 mA = 100%
0 to 1 V = 0%
0 to 1 V = 0%
5 V = 100%
5 V = 100%
0 to 2 V = 0%
0 to 2 V = 0%
10 V = 100%
10 V = 100%
0 to 4 mA = 0%
0 to 4 mA = 0%
20 mA = 100%
20 mA = 100%
PU operation
External operation
ANALOG VALUE 310
PID control disabled
Pr.133 setting /
ANALOG VALUE 310
Pr.133 setting /
Pr.133 setting / External
*3
External terminal
terminal
PU operation
External operation
PID control disabled
ANALOG VALUE 311
*6
(terminal 4)
*8
External terminal
External terminal
Result
Deviation
0 V = 0%
5 V = 100%
0 V = 0%
10 V = 100%
0 mA = 0%
20 mA = 100%
0 V = -20%
1 V = 0%
5 V = 100%
0 V = -20%
2 V = 0%
10 V = 100%
0 mA = -20%
4 mA = 0%
20 mA = 100%
Network operation
BACnet/IP
communication
Communication (PID set
*4
point)
Pr.133 setting /
Communication (PID set
*3
*3*4
point)
Pr.133 setting / External
*3
*3
terminal
Network operation
BACnet/IP
communication
Communication (PID
measured value)
*8
External terminal
Calibration parameter
Pr.125, C2 to C4 (Pr.902,
Pr.903)
Pr.126, C5 to C7 (Pr.904,
Pr.905)
page
PLC function
Other
*1
Pr.133 setting /
*2*3
SD1248
PLC function
Other
*5
*6
*7
SD1249
*8
16. (A) Application Parameters
16.4 PID control
11
12
13
14
15
350.)
16
17
18
19
20
425

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents