11.6

Operation by multi-speed setting

Use these parameters to change among pre-set operation speeds with the terminals. The speeds are pre-set with parameters.
Any speed can be selected by simply turning ON/OFF the contact signals (RH, RM, RL, and REX signals).
Pr.
Name
4
Multi-speed setting (high speed) 60 Hz
D301
5
Multi-speed setting (middle
D302
speed)
6
Multi-speed setting (low speed)
D303
24
Multi-speed setting (speed 4)
D304
25
Multi-speed setting (speed 5)
D305
26
Multi-speed setting (speed 6)
D306
27
Multi-speed setting (speed 7)
D307
232
Multi-speed setting (speed 8)
D308
233
Multi-speed setting (speed 9)
D309
234
Multi-speed setting (speed 10)
D310
235
Multi-speed setting (speed 11)
D311
236
Multi-speed setting (speed 12)
D312
237
Multi-speed setting (speed 13)
D313
238
Multi-speed setting (speed 14)
D314
239
Multi-speed setting (speed 15)
D315
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
 Multi-speed setting (Pr.4 to Pr.6)
• The inverter operates at frequencies set in Pr.4 when the RH signal is ON, Pr.5 when the RM signal is ON, or Pr.6 when
the RL signal is ON.
Forward rotation start
Reverse rotation start
High speed
Middle speed
Low speed
Switch
NOTE
• In the initial setting, if two or more speed switches (signals) are simultaneously turned ON, priority is given to the switch (signal)
for the lower speed. For example, when both RH and RM signals turn ON, the RM signal (Pr.5) has the higher priority.
• The RH, RM and RL signals are assigned to the terminals RH, RM and RL, respectively, in the initial status. To assign each
signal to a different terminal, set "0" (RL signal), "1" (RM signal), or "2" (RH signal) in any of Pr.178 to Pr.189 (Input terminal
function selection).
*1
Initial value
Setting range
Gr.1
Gr.2
50 Hz
0 to 590 Hz
30 Hz
0 to 590 Hz
10 Hz
0 to 590 Hz
9999
0 to 590 Hz, 9999
page
54).
Inverter
STF
STR
RH
RM
RL
SD
Description
Sets the frequency when RH is ON.
Sets the frequency when RM is ON.
Sets the frequency when RL is ON.
Frequency from 4th speed to 15th speed can
be set according to the combination of the RH,
RM, RL and REX signals.
9999: Not selected
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
ON
RH
ON
RM
ON
RL
11. (D) Operation Command and Frequency Command
11.6 Operation by multi-speed setting
11
12
13
14
15
16
17
18
19
20
273

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents