NOTE
• The stop selection setting is disabled when the following functions are operating.
Position control
Power failure stop function (Pr.261)
PU stop (Pr.75)
Deceleration stop due to a communication error (Pr.502)
• When Pr.250 ≠ "9999 or 8888", acceleration/deceleration is performed in accordance to the frequency command until the
output is shut off by turning OFF the start signal.
• When the restart signal is turned ON during the motor coasting, the operation is resumed from Pr.13 Starting frequency.
• Even with the setting of coasting to a stop, when the LX signal is turned ON, the motor does not coast but zero speed control
or servo lock is applied.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration
Pr.13 Starting
frequencypage
244,
Pr.75 Reset selection/disconnected PU detection/PU stop
Pr.261 Power failure stop
selectionpage 455
Pr.502 Stop mode selection at communication error Instruction Manual (Communication)
timepage 232
page 245
selectionpage 197
483
17. (G) Control Parameters
17.7 Stop selection