2.
Press the PU/EXT key three times (the PS warning is reset)
when Pr.79 Operation mode selection = "0" (initial value) or "6".
When Pr.79 = "2, 3, or 7", the PU stop warning can be cleared with one keystroke.
• The inverter can be restarted by performing the reset operation (by turning OFF and ON the power or inputting the RES
signal).
NOTE
• Even when Pr.250 Stop selection ≠ "9999" is set and coasting stop is selected, using the PU stop function in the External
operation mode does not provide coasting stop but deceleration stop.
Reset limit (P.E107) (for the safety communication model only)
• When "10" is set in P.E107 or any value from "10000 to 10003, 10014 to 10017" is set in Pr.75, the reset command input
(using the STOP/RESET key or the RES signal) is disabled when the protective function (E.SAF) is activated. Turn ON the
power supply of the inverter again to reset the inverter.
NOTE
• When a communication option is installed, reset is enabled when the protective function (E.SAF) is activated regardless of
P.E107 or Pr.75 setting.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which
is dangerous.
Parameters referred to
Pr.79 Operation mode
selectionpage 250
Pr.250 Stop
selectionpage 482
Pr.551 PU mode operation command source
Speed
Operation
panel
STF
ON
(STR) OFF
Stop/restart example for External operation
selectionpage 261
Time
Key
Key
9. (E) Environment Setting Parameters
9.2 Reset selection / disconnected PU detection / PU stop selection