Position adjustment parameter settings

Vector
Vector
Vector
Pr.
Name
426
In-position width
B007
427
Excessive level error
B008
510
Rough match output
B196
range
1294
Position detection lower
B192
4 digits
1295
Position detection upper
B193
4 digits
1296
Position detection
B194
selection
1297
Position detection
B195
hysteresis width
 In-position width (Pr.426, Y36 signal)
• The Y36 signal is used as the In-position signal.
• If the number of droop pulses (after electronic gear) reaches the Pr.426 setting value or smaller, the In-position (Y36) signal
turns ON. (The number of droop pulses (after electronic gear) is calculated by subtracting the current position (after
electronic gear) from the position command (after electronic gear).)
• To use the Y36 signal, set "36 (positive logic)" or "136 (negative logic)" in any parameter from Pr.190 to Pr.196 (Output
terminal function selection) to assign the function.
 Excessive level error (Pr.427)
• If the number of droop pulses (after electronic gear) reaches the Pr.427 setting value or smaller, E.OD (Excessive position
fault) is activated and the inverter output is shutoff. (The number of droop pulses (after electronic gear) is calculated by
subtracting the current position (after electronic gear) from the position command (after electronic gear).) Increase the error
threshold level when a small value is set as the Pr.422 Position control gain setting value. Set a small value for early
detection even when the load is heavy.
• If Pr.427 = "9999", E.OD is not activated regardless of the amount of droop pulses.
 During position command operation signal (PBSY signal)
• The During position command operation (PBSY) signal turns ON during position command operation. To use the PBSY
signal, set "61 (positive logic)" or "161 (negative logic)" in any parameter from Pr.190 to Pr.196 (Output terminal function
selection) to assign the function.
Initial value
Setting range
100 pulses
0 to 32767 pulses
0 to 400K
40K
9999
0
0 to 32767
0
0 to 9999
0
0 to 9999
0
0
1
2
0
0 to 32767
Description
Set the number of droop pulses that triggers the In-position
(Y36) signal.
Set the number of droop pulses that activates Excessive
position fault (E.OD).
Function disabled
Set the remaining command distance at which the Rough
match (CPO) signal is output.
Set the lower four digits of the position detection value.
Set the upper four digits of the position detection value.
The position is detected on both the plus and minus sides.
The position is detected on the plus side only.
The position is detected on the minus side only.
Set the hysteresis width for the detected position where the
Position detection level (FP) signal turns ON.
7.6 Position adjustment parameter settings
1
2
3
4
5
6
7
8
9
10
179
7. Position Control