• Use C40 (Pr.933) to set the torque to the 20 mA input of the torque command current (0 to 20 mA).
400
150
Bias
C38(Pr.932)
0
0
C39(Pr.932)
Calibration example of terminal 4
• There are three methods to adjust the bias/gain for torque setting current (voltage).
Adjustment by applying current (voltage) between terminals 4 and 5 to set the current (voltage) at the bias/gain torque.
page 365
Adjustment by selecting the current (voltage) at the bias/gain torque without applying current (voltage) between terminals
page 366
4 and 5.
Adjustment by changing the torque without adjusting the current (voltage).
NOTE
• Always calibrate the input after changing the voltage/current input signal with Pr.267 and the voltage/current input selection
switch.
 Display unit changing for analog input (Pr.241)
• The analog input display unit (%/V/mA) can be changed for analog input bias/gain calibration.
• Depending on the terminal input specification setting of Pr.73 (Pr.267), the units of the displayed values of C39 (Pr.932)
and C41 (Pr.933) change as shown below:
Analog command (via terminal 4)
(depending on the Pr.267 setting)
0 to 5 V input
0 to 10 V input
0 to 20 mA input
364
14. (T) Multi-Function Input Terminal Parameters
14.5 Torque (magnetic flux) setting current (voltage) bias and gain
Initial value
100%
Torque setting signal
20mA
C41(Pr.933)
Pr.241 = "0" (initial value)
0% to 100% (0.1%)
0% to 100% (0.1%)
0% to 100% (0.1%)
Gain
C40(Pr.933)
page 367
Pr.241 = "1"
0 to 5 V (0.01 V)
0 to 10 V (0.01 V)
0 to 20 mA (0.01 mA)