4.2.10 Jog operation (Pr. 15, Pr. 16)

Pr. 15 "jog frequency"
Pr. 16 "jog acceleration/deceleration time"
In the external operation mode, jog operation can be started and stopped by the start signal (STF, STR) with
the jog signal ON, after selection of the jog operation function using the input terminal function selection. In
the PU operation mode, jog operation can also be performed using the PU (FR-DU04/FR-PU04).
Set the frequency and acceleration/deceleration time for jog operation
Parameter Number
Factory Setting
15
16
Output frequency (Hz)
Pr.20
Jog frequency
Forward
Pr.15
setting range
rotation
Pr.16
JOG signal
Forward rotation STF
ON
Reverse rotation STR
Note: 1. In S-shaped acceleration/deceleration pattern A, the set time is a period of time required to reach
Pr. 3 "base frequency".
2. The acceleration time and deceleration time cannot be set separately for jog operation.
3. The value set in Pr.15 "jog frequency" should be equal to or greater than the Pr.13 "starting
frequency" setting.
Setting Range
5Hz
0 to 400Hz
0 to 3600 s
0.5 s
0 to 360 s
Time
Reverse
rotation
ON
ON
Get other manuals https://www.bkmanuals.com
Related parameters
Pr. 20 "acceleration/deceleration
reference frequency"
Pr. 21 "acceleration/deceleration time
increments"
Pr. 79 "operation mode selection"
Pr. 180 to Pr. 186
(input terminal function selection)
Remarks
When Pr. 21 = 0
When Pr. 21 = 1
82
PARAMETERS