Frequency Setting By External Terminals; Operation By Multi-Speed Operation (Pr. 4 To Pr. 6, Pr. 24 To Pr. 27, Pr. 232 To Pr. 239); Jog Operation (Pr. 15, Pr. 16) - Mitsubishi Electric FR-D720-070 Instruction Manual

Table of Contents

Advertisement

4.6

Frequency setting by external terminals

Purpose
Make frequency setting by
Multi-speed operation
combination of terminals
Perform Jog operation
Jog operation
Infinitely variable speed setting by
Remote setting function
terminals
4.6.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
Parameter
Name
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24 ∗
Multi-speed setting (speed 4)
25 ∗
Multi-speed setting (speed 5)
26 ∗
Multi-speed setting (speed 6)
27 ∗
Multi-speed setting (speed 7)
232 ∗
Multi-speed setting (speed 8)
233 ∗
Multi-speed setting (speed 9)
234 ∗
Multi-speed setting (speed 10)
235 ∗
Multi-speed setting (speed 11)
236 ∗
Multi-speed setting (speed 12)
237 ∗
Multi-speed setting (speed 13)
238 ∗
Multi-speed setting (speed 14)
239 ∗
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
* The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Speed 1
(High speed)
Speed 5
Speed 6
Speed 2
(Middle speed)
Speed 4
Speed 3
(Low speed)
Speed 7
ON
ON
ON ON
RH
ON
ON
ON
ON
RM
ON
ON
ON
RL
REMARKS
In the initial setting, if two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency of
the lower signal.
For example, when the RH and RM signals turn on, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By setting "0 (RL)", "1 (RM)", "2 (RH)" in
any of Pr. 178 to Pr. 182 (input terminal function selection), you can assign the signals to other terminals.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Frequency setting by external terminals

Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 15, Pr. 16
Pr. 59
Initial Value
Setting Range
60Hz
0 to 400Hz
Frequency when RH turns on
30Hz
0 to 400Hz
Frequency when RM turns on
10Hz
0 to 400Hz
Frequency when RL turns on
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
Frequency from 4 speed to 15 speed can
9999
0 to 400Hz, 9999
be set according to the combination of
9999
0 to 400Hz, 9999
the RH, RM, RL and REX signals.
9999
0 to 400Hz, 9999
9999: not selected
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
(1) 3-Speed setting (Pr. 4 to Pr. 6)
The inverter operates at frequencies set in Pr. 4 when RH signal is on,
Pr. 5 when RM signal is on and Pr. 6 when RL signal is on.
Time
Refer to Page
89
91
93
Description
4
89