Mitsubishi Electric 800 Series Instruction Manual (Function page 371

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Signal
Setting
name
76
X76
87
X87
88
LSP
89
LSN
92
X92
9999
*1
When Pr.59 Remote function selection ≠ "0", functions of the RL, RM, and RH signals are changed as shown in the table.
*2
When Pr.270 Stop-on-contact control selection = "1 or 11", functions of the RL and RT signals are changed as shown in the table.
*3
The OH signal is activated when the relay contact is open.
*4
For details, refer to the PLC Function Programming Manual.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• The priorities of the speed commands are defined as follows: JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the Inverter run enable (X10) signal is not assigned, or when the PU operation external interlock (X12) signal is not
assigned while Pr.79 Operation mode selection = "7", the MRS signal performs the same function.
• The same terminals are used to assign the multi-speed (7-speed) setting and the remote setting. The multi-speed setting and
the remote setting cannot be assigned separately.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
 Parameters available for each signal
• The following table shows the parameters to which the signals are assigned.
Setting
Signal
value
name
0
RL
1
RM
2
RH
3
RT
4
AU
5
JOG
7
OH
8
REX
10
X10
12
X12
13
X13
14
X14
15
BRI
16
X16
18
X18
23
LX
24
MRS
STP
25
(STOP)
26
MC
27
TL
30
JOG
37
X37
42
X42
43
X43
46
TRG
47
TRC
50
SQ
51
X51
370
14. (T) Multi-Function Input Terminal Parameters
14.6 Input terminal function selection
Function
Proximity dog
Sudden stop
Forward stroke end
Reverse stroke end
Emergency stop
No function
FR-E800
Pr.180 to
Pr.178
Pr.179
Pr.184
Pr.511, Pr.1282, Pr.1283,
Pr.1285, Pr.1286
Pr.464 to Pr.478
Pr.1292
Pr.1292
Pr.1103
FR-E800-E
Pr.185 to
Pr.178
Pr.179
Pr.189
Refer to
Related parameter
page
167
170
170
170
232
FR-E800-
SCE
Pr.180 to
Pr.180 to
Pr.189
Pr.189

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents