*1
Power is measured in the range of 0 to 99999.99 kWh, and displayed in 4 digits. After the watt-hour meter (cumulative power counter) reaches
"99.99" (999.99 kWh), the meter displays values in 0.1 increments such as "100.0" (1000.0 kWh). Use Pr.891 to shift the decimal point position
when the monitored value becomes equal to or higher than 10000 kWh.
• The decimal point position on the watt-hour meter can be shifted to left. The number of digits to be shifted is equal to the
setting of Pr.891 Cumulative power monitor digit shifted times. For example, when Pr.891 = "2", the cumulative power
value 1278.56 kWh is displayed as 12.78 (in 100 kWh increments) on the operation panel, or displayed as 12 on a display
used for monitoring via communication.
• When Pr.891 = "0 to 4", the meter stops at the maximum number. When Pr.891 = "9999", the meter returns to 0 and the
counting starts again.
• The cumulative power can be monitored as 32-bit data via communication by setting Pr.52 = "77 to 80". The maximum
monitored value is 42949672 kWh in 1 kWh increments or 42949672.94 kWh in 0.01 kWh increments. Pr.891 setting is
invalid while 32-bit cumulative power is monitored. (For details on communication for 32-bit cumulative power monitor, refer
to the Instruction Manual (Communication) or the Instruction Manual of the communication option.)
• Writing "0" in Pr.170 clears the cumulative power monitor.
NOTE
• When Pr.170 is read just after "0" has been written in Pr.170, the setting "9999" or "10" is displayed.
 Monitoring cumulative energization time (Pr.563)
• When the cumulative energization time is selected as a monitor item (Pr.52 = "20"), the counter of cumulative energization
time since the inverter shipment accumulated every hour is displayed.
• One hour is displayed as "0.001", and the value is counted up to "65.53".
• The EEPROM is updated every minute until the cumulative energization time reaches one hour, and then the EEPROM is
updated every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the cumulative
energization time counter reaches 65535 can be checked with Pr.563.
NOTE
• The cumulative energization time does not increase if the power is turned OFF after less than an hour.
 Actual operation time monitoring (Pr.171, Pr.564)
• On the actual operation time monitoring (Pr.52 = "23"), the inverter running time is added up every hour. (Time is not added
up during a stop.)
• One hour is displayed as "0.001", and the value is counted up to "65.53".
• The values are stored in EEPROM every 10 minutes. The EEPROM is also updated at power OFF.
• When the cumulative energization time counter reaches 65535, it starts from 0 again. The number of times the actual
operation time counter reaches 65535 can be checked with Pr.564.
• Setting "0" in Pr.171 clears the actual operation time meter.
NOTE
• The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
• Once "0" is set in Pr.171, the setting of Pr.171 is always turned to "9999" afterwards. Setting "9999" does not clear the actual
operation time meter.
 Hiding the decimal places for the monitors (Pr.268)
• The numerical figures after a decimal point displayed on the operation panel may fluctuate during analog input, etc. The
decimal places can be hidden by selecting the decimal digits with Pr.268.
Pr.268 setting
9999 (initial value) No function
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers
0
in the first decimal place and smaller are rounded to display an integral value (1 increments). The
monitor value equal to or smaller than 0.99 is displayed as 0.
When monitoring with the second decimal place (0.01 increments), the 0.01 decimal place is
1
dropped and the monitor displays the first decimal place (0.1 increments). When monitoring with the
first decimal place, the display will not change.
Description
13. (M) Item and Output Signal for Monitoring
13.2 Monitor item selection on operation panel or via communication
11
12
13
14
15
16
17
18
19
20
317

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents