14
(T) Multi-Function Input Terminal Parameters
Purpose
To inverse the rotation direction with the
voltage/current analog input selection
(terminals 2 and 4)
To assign functions to analog input
terminals
To eliminate noise on analog inputs
To adjust analog input frequency/voltage
(current) (calibration)
To adjust analog input torque/voltage
(current) (calibration)
To assign functions to input terminals
To change the input specification (NO/NC
contact) of input signals
To assign start and forward/reverse
commands to different signals
14.1

Analog input selection

The functions to switch the analog input terminal specifications and forward/reverse rotation by the input signal polarity are
selectable.
Pr.
73
Analog input selection
T000
267
Terminal 4 input
T001
selection
350
14. (T) Multi-Function Input Terminal Parameters
14.1 Analog input selection
Analog input selection
Terminal 4 function assignment P.T040
Analog input filter
Frequency setting voltage
(current) bias and gain
Torque setting voltage (current)
bias and gain
Input terminal function
selection
Output stop signal (MRS) /
Inverter run enable signal (X10)
input selection
Start signal (STF/STR) operation
selection
Name
Initial value
1
0
Parameter to set
P.T000, P.T001
P.T002 to P.T007
P.T200 to P.T203,
P.T400 to P.T403,
P.M043
P.T410 to P.T413,
P.M043
P.T700 to P.T711,
P.T740
P.T720
P.G106
Setting
range
Switch 2: V (initial
0, 1, 10, 11
status)
6, 16
Switch 2: I
Switch 4: I (initial
0
status)
1
Switch 4 - V
2
Pr.73, Pr.267
Pr.858
Pr.74, Pr.822, Pr.826,
Pr.832, Pr.836,
Pr.849
Pr.125, Pr.126,
Pr.241, C2 to C7
(Pr.902 to Pr.905)
Pr.241, C38 to C41
(Pr.932, Pr.933)
Pr.178 to Pr.189,
Pr.699
Pr.17
Pr.250
Description
The terminal 2 input specification (0 to 5 V, 0 to 10
V, 0 to 20 mA) is selectable. Also the reversible
operation setting is selectable.
Terminal 4 input, 4 to 20 mA
Terminal 4 input, 0 to 5 V
Terminal 4 input, 0 to 10 V
Refer to
page
350
355
356
358
363
368
372
376