• When the inverter decelerates to the frequency set to Pr.282 Brake operation frequency during deceleration, the inverter
turns OFF the brake opening request signal (BOF) and decelerates further to the frequency set in Pr.278. And after the
time set in Pr.283 Brake operation time at stop passes, the inverter decelerates again. The inverter output is shut off
when the frequency reaches Pr.13 Starting frequency setting or 0.5 Hz, whichever is lower.
Output frequency(Hz)
Output current or motor torque
Brake opening request
Electromagnetic brake
NOTE
• Even if the brake sequence operation has been selected, inputting the JOG signal (JOG operation) during an inverter stop
changes the operation method to normal operation and give a priority to the JOG operation. Note that the JOG signal input by
the brake sequence function is invalid during operation.
 Protective function
• If one of the following faults occurs while the brake sequence function is enabled, the inverter enters a fault status, shuts
off output, and turns OFF the brake opening request signal (BOF).
Fault
indication
When (detection frequency) - (output frequency) > Pr.285 during encoder feedback control. (Overspeed detection function)
E.MB1
When Pr.285 = "9999", overspeed is not detected.
When deceleration is not normal during deceleration operation from the set frequency to the frequency set in Pr.282 (when
E.MB2
Pr.284 = "1") (except stall prevention operation).
When Pr.284 = "0", deceleration is not detected.
E.MB3
When the BOF signal turned ON while the motor is at a stop. (Load slippage prevention function)
When 2 seconds or more have elapsed after the start command (forward or reverse rotation) is input, but the BOF signal
E.MB4
does not turn ON.
E.MB5
When 2 seconds or more have elapsed after the BOF signal turned ON, but the BRI signal does not turn ON.
E.MB6
When the inverter had turned ON the brake opening request signal (BOF), but the BRI signal turned OFF.
E.MB7
When 2 seconds or more have elapsed after the BOF signal turned OFF at a stop, but the BRI signal does not turn OFF.
Target frequency
Pr.280
Pr.282
Pr.278
Pr.13
STF
Pr.279
(select by Pr.639)
(BOF signal)
Closed
operation
Pr.13 setting
or 0.5Hz,
Pr.281
whichever is lower
Pr.283
ON
ON
Opened
Closed
Description
Time
16. (A) Application Parameters
16.1 Brake sequence function
11
12
13
14
15
16
17
18
19
20