Mitsubishi Electric 800 Series Instruction Manual (Function page 337

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Setting
Positive
Negative
logic
logic
96
196
REM
98
198
LF
99
199
ALM
206
306
Y206
211
311
LUP
212
312
LDN
213
313
Y213
242
342
LNK
9999
*1
Note that changing the frequency setting with an analog signal or the setting dial on the operation panel may cause the turning ON and OFF of
Up to frequency (SU) signal depending on its changing speed and the timing of the speed change determined by the acceleration/deceleration
time setting. (The signal state changing does not occur when the acceleration/deceleration time is set to 0 second.)
*2
Available when the plug-in option is connected.
NOTE
• One function can be assigned to more than one terminal.
• The function works during the terminal conducts when the parameter setting is any of "0 to 99, 200 to 299", and the function
works during the terminal does not conduct when the setting is "100 to 199, 300 to 399".
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• Do not assign the signal to terminals A, B, and C which frequently changes its state between ON and OFF. Otherwise, the life
of the relay contact may be shortened.
 Adjusting the output terminal response level (Pr.289)
• The responsivity of the output terminals can be delayed in a range between 5 to 50 ms. (The following is the operation
example of the RUN signal.)
RUN
Pr.289 = 9999
RUN
Pr.289 ≠ 9999
NOTE
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output after the time
period calculated by adding the Pr.289 setting to the Pr.157 setting elapsed.
• The signal output for the PLC function (see
by the Pr.289 setting (not filtered for responsivity).
336
13. (M) Item and Output Signal for Monitoring
13.6 Output terminal function selection
Signal
Function
name
Remote output
Alarm
Fault
Cooling fan operation
command
Upper limit warning
detection
Lower limit warning
detection
During load
characteristics
measurement
Inverter-to-inverter linkup
No function
ON
ON
Pr.289
Operation
Output via a terminal by setting a proper
number in a relative parameter.
Output when an Alarm fault (fan fault or a
communication error) occurs.
Output when the inverter's protective
function is activated to stop the power output
(when the Fault occurs). The signal output
stops when the inverter reset starts.
Output when the cooling fan operation is
commanded.
Output when the load fault upper limit
warning is detected.
Output when the load fault lower limit
warning is detected.
Output during measurement of the load
characteristics.
Output when the inverter receives a
response from all the slave inverters during
initial communication, or when the inverter
returns a response to the master. (Available
for the Ethernet model and the safety
communication model only.)
Time
OFF
OFF
Pr.289
page
457) and the remote output signal via BACnet communication are not affected
Related
Refer to page
parameter
Pr.495 to
347
Pr.497
Instruction
Manual
Pr.121, Pr.244
(Communication)
,
284
340
Pr.244
284
Pr.1480 to
300
Pr.1492
Instruction
Pr.1124,
Manual
Pr.1125
(Communication)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents