12.3
Earth (ground) fault detection at start
Select whether to make earth (ground) fault detection at start. When enabled, earth (ground) fault detection is performed
immediately after a start signal input to the inverter.
Pr.
249
Earth (ground) fault detection at
H101
start
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
• If a ground fault is detected at start while Pr.249 = "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off.
• When the Pr.72 PWM frequency selection setting is high, enable the ground fault detection at start.
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use Pr.249 to enable/disable ground fault detection at operation start.
Initial value
Name
Gr.1
0
*1
Setting range
Gr.2
Earth (ground) fault detection at start
0
disabled
1
Earth (ground) fault detection at start
1
enabled
page
54).
12.3 Earth (ground) fault detection at start