Automatic Restart After Instantaneous Power Failure / Flying Start With An Induction Motor - Mitsubishi Electric 800 Series Instruction Manual (Function

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

16.7
Automatic restart after instantaneous power failure
/ flying start with an induction motor
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless Vector
Sensorless
The inverter can be restarted without stopping the motor operation in the following situations:
• When an instantaneous power failure occurs during inverter running
• When the motor is coasting at start
Pr.
Name
Automatic restart after
162
instantaneous power
A700
failure selection
Rotation direction
299
detection selection at
A701
restarting
57
Restart coasting time
A702
58
Restart cushion time
A703
165
Stall prevention operation
A710
level for restart
611
Acceleration time at a
F003
restart
*1
The coasting time when Pr.57 = "0" is as shown below. (When Pr.162 and Pr.570 are set to the initial value.)
0.5 s for the FR-E860-0027(1.5K) or lower.
1 s for the FR-E820-0080(1.5K) or lower, FR-E840-0040(1.5K) or lower, FR-E860-0040(2.2K) or higher, and FR-E820S-0080(1.5K) or lower.
2 s for the FR-E820-0110(2.2K) to FR-E820-0330(7.5K), FR-E840-0060(2.2K) to FR-E840-0170(7.5K), and FR-E820S-0110(2.2K).
3 s for the FR-E820-0470(11K) or higher and FR-E840-0230(11K) or higher.
• To operate the inverter with the automatic restart after instantaneous power failure function enabled, check the following
points.
• Set Pr.57 Restart coasting time = "0".
Vector
Vector
Initial
Setting
value
range
0
Frequency search only performed at the first start
Reduced voltage start only at the first start (no frequency search) or encoder
1
detection frequency search
0
10
Frequency search at every start
Reduced voltage start at every start (no frequency search) or encoder
11
detection frequency search
0
Rotation direction detection disabled
1
Rotation direction detection enabled
When Pr.78 Reverse rotation prevention selection = "0", with rotation
0
direction detection
9999
When Pr.78 Reverse rotation prevention selection = "1 or 2", without
rotation direction detection
0
Coasting time differs according to the inverter capacity.
Set the time delay for the inverter to perform a restart after restoring power
9999
0.1 to 30 s
due to an instantaneous power failure.
9999
No restart
1 s
0 to 60 s
Set the voltage cushion time for restart.
Set the stall prevention level at restart operation on the assumption that the
150%
0% to 400%
inverter rated current is 100%.
Set the acceleration time to reach Pr.20 Acceleration/deceleration
0 to 3600 s
reference frequency at restart.
9999
Standard acceleration time (for example, Pr.7) is applied as the acceleration
9999
time at restart.

16.7 Automatic restart after instantaneous power failure / flying start with an induction motor

Description
*1
16. (A) Application Parameters
11
12
13
14
15
16
17
18
19
20
443

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800 seriesFr-e800Fr-e820-0008Fr-e840-0016Fr-e860-0017Fr-e820s-0008 ... Show all

Table of Contents