Interface Description - X03; Setting The Address - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Wiring
4.14 Connecting to AS-i
4.14.2

Interface description - X03

M12 A-coding connector
X03 - AS-i, 5-pin, male
Requirements for applications in USA and Canada
Use a NEC Class 2 or a limited voltage/limited current power supply as an external 24 V DC
voltage source.
Further information
Further connection information can be found in the AS-Interface system manual.
4.14.3

Setting the address

As factory setting, all AS-i slaves have address 0. Slaves with address 0 are not included in the
communication.
The addresses must be unique, although they can be mixed as required.
You have the following options when making the address assignment:
• Automatic addressing via the AS-i master
• Addressing via the addressing device
• Addressing via parameters
Before you set the address, you must specify whether the converter is integrated as Single
Slave or Dual Slave in the AS-i network.
• p2013 = 0: Single Slave (factory setting)
• p2013 = 2: Dual Slave
If you select the Single Slave macro (Macro 30 or 66) or the Dual Slave macro (Macro 31 or
34) during the commissioning, the AS-i mode p2013 is automatically assigned to the
appropriate value.
Note
Changes made to p2012 and p2013
Changes made to the p2012 and p2013 parameters take effect immediately after the change.
If you work with a commissioning tool, you must back up the changes so they are not lost
when the system is switched off and on again.
90
Pin
1
2
3
4
5
Overview of the manuals (Page 542)
Signal
Description
AS-i +
AS-i positive
AUX -
Auxiliary 0 V
AS-i -
AS-i negative
AUX +
Auxiliary 24 V
FE
Not connected
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
SINAMICS G115D distributed drive