Selecting the fixed speed setpoint, binary
p1020
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Example
After it has been switched on, a conveyor belt only runs with two different velocities. The
motor should now operate with the following corresponding speeds:
• The signal at digital input 0 switches the motor on and accelerates it up to 300 rpm.
• The signal at digital input 1 accelerates the motor up to 2000 rpm.
• With signals at both digital inputs, the motor accelerates up to 2300 rpm.
Settings for the application example
Parameter
p1001[0] =
300.000
p1002[0] =
2000.000
p0840[0] = 722.0
p1070[0] = 1024
p1020[0] = 722.0
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
p1021
p1022
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
Description
Fixed speed setpoint 1
Fixed speed setpoint 2
ON/OFF1: Switches on the motor with digital input 0
Main setpoint: Interconnects the main setpoint with a fixed speed setpoint.
Fixed speed setpoint selection, bit 0: Interconnects fixed speed setpoint 1 with
digital input 0 (DI 0).
p1023
Resulting setpoint
0
0
0
p1001
0
p1002
0
p1003
0
p1004
0
p1005
0
p1006
0
p1007
1
p1008
1
p1009
1
p1010
1
p1011
1
p1012
1
p1013
1
p1014
1
p1015
Advanced commissioning
6.15 Setpoints