Commissioning

5.4 Quick commissioning

5.4
Quick commissioning
5.4.1

Quick commissioning with DIP switches

Overview
The G115D converters have been designed to allow quick commissioning to be performed
using two sets of DIP switches. The DIP switches are located on the Wiring Module. To access
the DIP switches, you must first remove the Electronic Module.
Accessing the DIP switches
Electric shock caused by dangerous voltages and currents in the active converter
When power is applied to the converter, even when it is not active, dangerous levels of
voltage and current are present in the system.
Before attempting the removal of any components of the system, the following steps should
be taken to ensure that the system is completely safe:
1. Disconnect all mains power supplies (line supply and external 24 V power supply) to the system.
2. Wait five minutes to allow all the residual current and voltages to dissipate fully.
3. Check the voltage at the converter connections before removing any component.
Release the retaining screws (6 x M4) for the Electronic Module by using a 3 mm allen key,
and then remove the module, as shown in the figure below:
Note
Reattach the screws with a tightening torque of 2.5 Nm (22.1 lbf.in).
106
WARNING
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
SINAMICS G115D distributed drive