Checking The Interconnection Of Digital Inputs - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Parameters
Parameter
p0010
p0971
p9700
p9701
6.14.2.8

Checking the interconnection of digital inputs

Overview
The simultaneous connection of digital inputs with a safety function and a "standard"
function may lead to the drive behaving in unexpected ways.
If you control the safety functions in the converter via fail-safe digital inputs, then you must
check as to whether the fail-safe digital inputs are in some instances interconnected with a
"standard" function.
Function description
Procedure
1. Select the screen for the digital inputs.
2. Remove all interconnections of the digital inputs that you use as fail-safe digital input F-DI:
3. You must delete the digital input connections for all CDS if you use the switchover of the
command data sets (CDS).
You can find a description of the CDS switchover in the operating instructions.
You have ensured that the fail-safe digital inputs only control the safety functions in the
converter.
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Description
Drive commissioning parameter filter 0: Ready
Save parameters
SI Motion copy function
Acknowledge SI motion data change
Advanced commissioning
6.14 Safe Torque Off (STO) safety function
Setting
1: Save the drive object
(copy from RAM to ROM)
After the converter has saved the parameters in
a non-volatile fashion, then p0971 = 0.
Start the SI parameter copy function.
Factory setting: 0
Confirm SI Basic parameter change
Factory setting: 0
227