Advanced commissioning
6.25 Monitoring the driven load
Setting pump monitoring
1. Set p2193 = 4.
2. The converter sets the monitoring as shown.
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. If necessary, adjust the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
Setting fan and compressor monitoring
1. Set p2193 = 5.
2. The converter sets the monitoring as shown.
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
296
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
SINAMICS G115D distributed drive