Advanced commissioning
6.25 Monitoring the driven load
Setting pump monitoring
1. Set p2193 = 4.
2. The converter sets the monitoring as shown.
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. If necessary, adjust the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
❒
Setting fan and compressor monitoring
1. Set p2193 = 5.
2. The converter sets the monitoring as shown.
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
❒
296
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002