6.4.1

Two-wire control, method 1

Command "ON/OFF1" switches the motor on and off. The "Reversing" command inverts the
motor direction of rotation.
Parameters
Select two-wire control, method 1
Parameter
p0015 = 60
Changing the assignment of the digital inputs
Parameter
p0840[0...n] = 722.x
p1113[0...n] = 722.x
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
6.4 Controlling clockwise and counter-clockwise rotation via digital inputs
ON/OFF1
Reversing
0
0
0
1
1
0
1
1
Description
Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: ON/OFF1
DI 1: Reversing
Description
BI: ON/OFF1 (ON/OFF1)
Example: p0840 = 722.3 ⇒ DI 3: ON/OFF1
BI: Setpoint inversion (reversing)
Function
OFF1: The motor stops
ON: Clockwise motor rotation
ON: Counter-clockwise motor rotation