Example
As in the example above, you obtain the interconnection if you configured the interfaces of
the converter accordingly.
An overview of all the parameters that belong to the command data sets is provided in the
List Manual.
Note
The converter requires approximately 4 ms to switch over the command data set.
Parameters
Parameter
p0010
r0050.0...1
p0170
p0809[0...2]
p0810
p0811
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
6.10 Switching over the drive control (command data set)
Description
Drive commissioning parameter filter
CO/BO: Command Data Set CDS effective
Number of command data sets (CDS)
Copy command data set CDS
BI: Command data set selection CDS bit 0
BI: Command data set selection CDS bit 1
Advanced commissioning
Setting
Set p0010 = 15 to change the data set.
Factory setting: 1
Displays the number of the currently active com-
mand data set
p0170 = 2, 3 or 4
Factory setting: 2
[0] Source command data set
[1] Target command data set
[2] 0→1: Starts the copy operation
Factory setting: 0
Sets the signal source to select CDS bit 0.
Factory setting: dependent upon the converter
Sets the signal source to select CDS bit 1.
Factory setting: 0