Advertisement

Advanced commissioning
6.15 Setpoints
Parameter
p1021[0] = 722.1
p1016 = 1
Resulting fixed speed setpoints for the application example
Fixed speed setpoint selected via
DI 0 = 0
DI 0 = 1 and DI 1 = 0
DI 0 = 1 and DI 1 = 1
Parameters
Parameter
p1001[0...n]
p1002[0...n]
...
p1015[0...n]
p1016
p1020[0...n]
p1021[0...n]
p1022[0...n]
p1023[0...n]
r1024
r1025.0
Further information
Additional information about binary and direct selection can be found in function diagrams
3010 and 3011 in the List Manual.
238
Description
Fixed speed setpoint selection, bit 1: Interconnects fixed speed setpoint 2 with
digital input 1 (DI 1).
Fixed speed setpoint mode: Directly selects fixed speed setpoints.
Description
CO: Fixed speed setpoint 1 [rpm]
CO: Fixed speed setpoint 2 [rpm]
...
CO: Fixed speed setpoint 15 [rpm]
Fixed speed setpoint selection mode Fixed speed setpoint mode
Fixed speed setpoint selection, bit 0 Fixed speed setpoint selection, bit 0
Fixed speed setpoint selection, bit 1 Fixed speed setpoint selection, bit 1
Fixed speed setpoint selection, bit 2 Fixed speed setpoint selection, bit 2
Fixed speed setpoint selection, bit 3 Fixed speed setpoint selection, bit 3
Fixed speed setpoint active
Fixed speed setpoint status
Resulting setpoint
Motor stops
300 rpm
2300 rpm
Setting
Fixed speed setpoint 1
Factory setting: 0 rpm
Fixed speed setpoint 2
Factory setting: 0 rpm
...
Fixed speed setpoint 15
Factory setting: 0 rpm
Factory setting: 1
1: Direct
2: Binary
Factory setting: 0
Factory setting: 0
Factory setting: 0
Factory setting: 0
Fixed speed setpoint is active.
Fixed speed setpoint status
1 signal: Fixed speed setpoint is selected.
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
SINAMICS G115D distributed drive