Table 3-1 Interface Description; Table 3-2 Optical Indicator - Siemens SINAMICS PERFECT HARMONY GH150 6SL3826 Operating Instructions Manual

Medium-voltage drive
Table of Contents

Advertisement

Interface assignment
X1 power input
X2 signal output
X6 power output channel 1
X7 power output channel 2
X8 power output channel 3
X9 power output channel 4
Table 3-1
Interface description
Interface
Manufacturer's designation
Mating connector
-X1
FRONT-MSTB 2,5/ 5-STF-5,08 (Phoenix Contact)
-X2
FRONT-MSTB 2,5/ 4-STF-5,08 (Phoenix Contact)
-X6 ... -X9
FRONT-MSTB 2,5/ 3-STF-5,08 (Phoenix Contact)
Table 3-2
Optical indicator
LED
Red
X6 -- IA>
X7 -- IA>
X8 -- IA>
X9 -- IA>
Green
UA
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
The 4 channels are assigned to 4 red LEDs on the front panel. The LED that is associated with
the channel that caused the shutdown is continuously lit.
The LED goes dark after acknowledgment.
The green LED on the front panel is lit as long as the output voltage (in the specified range) is
available at the power inputs.
Pin
Assignment
Pin 1
L or L+
Pin 2
Not assigned
Pin 3
N or L-
Pin 4
Not assigned
Pin 5
PE
Pin 4
Relay connection 1 power input
Pin 5
Relay connection 2 power input
Pin 6
Relay connection 1 power output
Pin 7
Relay connection 2 power output
Pin 1
+55 V
Pin 2
GND
Pin 3
PE/shield connection
Pin 1
+55 V
Pin 2
GND
Pin 3
PE/shield connection
Pin 1
+55 V
Pin 2
GND
Pin 3
PE/shield connection
Pin 1
+55 V
Pin 2
GND
Pin 3
PE/shield connection
Description
3.7 Components
39

Advertisement

Table of Contents
loading

Table of Contents