Data backup and series commissioning
7.1 Transferring settings using a memory card
7.1.4

Activating message for a memory card that is not inserted

Function
The converter identifies whether a memory card is not inserted, and signals this state. The
message is deactivated in the converter factory setting.
Activate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 2
Message A01101 for a memory card that is not inserted is activated.
To cyclically signal to a higher-level control that a memory card is not inserted, interconnect
parameter r9401 to the send data of a PROFIdrive telegram of your choice.
Deactivate message
Procedure
1. Set p2118[x] = 1101, x = 0, 1, ... 19
2. Set p2119[x] = 3
Message A01101 for a memory card that is not inserted is deactivated.
Parameters
Parameter
p2118[0 ... 19]
p2119[0 ... 19]
r9401
310
Description
Setting
Change message type,
Selects faults or alarms for which the message type should
message number
be changed.
Factory setting: 0
Change message type
Sets the message type for the selected fault or alarm.
1: Fault (factory setting)
2: Alarm
3: No message
Safely remove memory
Displays the status of the memory card.
card status
Bit 00: Memory card inserted
Bit 01: Memory card activated
Bit 02: Siemens memory card
Bit 03: Memory card used as USB data storage medium
from the PC
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002