Siemens SINAMICS G115D Operating Instructions Manual page 213

Distributed drive for conveyor technology control
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

After the OFF2 command
After the OFF2 command, the converter issues the signal to immediately close the motor
holding brake, irrespective of the motor speed.
Commissioning a motor holding brake
Precondition
The motor holding brake is connected to the converter.
Load can fall if the motor holding brake function is incorrectly set
For applications with a suspended load, such as cranes and elevators, there is a danger to
life if the "Motor holding brake" function is not completely set or is incorrectly set.
• When commissioning the motor holding brake function, secure any suspended loads,
• Set the motor holding brake function according to the following description.
• After commissioning, check that the motor holding brake and the motor control function
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
WARNING
e.g. by applying the following measures:
– Lower the load down to the floor.
– Secure the dangerous area so that nobody can inadvertently enter it.
reliably.
Advanced commissioning
6.11 Motor holding brake
211