Commissioning
5.6 Restoring the factory settings
5.6.1

Restoring the factory settings/delivery condition (without safety functions)

Procedure with Startdrive
1. Go online with the converter.
2. Select the command as follows from the project tree:
3. For the G115D wall-mounted converter, select the menu option as follows to restore to the
factory settings:
For the G115D motor-mounted converter, select the menu option as follows to restore to
the delivery condition:
4. Click on the
5. Wait until the converter has been reset to the factory settings/delivery condition.
You have reset the converter to the factory settings/delivery condition.
Further information
For more information on restoring on the SINAMICS G120 Smart Access, see Section "Backup
and restore" in the SINAMICS G120 Smart Access Operating Instructions.