Goodrive20-EU series VFD
Function
Name
code
Upper-limit
P03.19
setting of
braking torque
Electromotion
torque
P03.20
upper-limit
setting via
keypad
Braking torque
upper-limit
P03.21
setting via
keypad
Flux
weakening
P03.22
coefficient in
constant power
zone
The lowest flux
weakening
P03.23
point in
constant power
zone
Detailed instruction of parameters
P03.21 sets P03.19)
1: Set via AI1 (100% relative to three times of
motor current)
2: Set via AI2 (same as above)
3: Set via AI3 (same as above)
4: Set via HDI (same as above)
5: Set via MODBUS communication (same as
above)
6 – 8: Reserved
Note: Setting mode 1 – 8, 100% corresponds to
three times of the motor current.
The function code is used to set the limit of the
torque.
Setting range: 0.0 – 300.0% (motor rated
current)
The usage of motor in flux weakening control.
Function code P03.22 and P03.23 are effective
at constant power. The motor will enter the flux
weakening state when running at rated speed.
Change the flux weakening curve by modifying
the flux weakening control coefficient. The bigger
the flux weakening control coefficient is, the
steeper the weakening curve is.
m
Min. limit
Setting range of P03.22: 0.1 – 2.0
Setting range of P03.23: 10% – 100%
Flux weakening
coefficient of the motor
0.10
1.00
2.00
51
Function parameters
Default
Modify
value
0
180.0%
180.0%
0.3
20%

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive20-EU VFD Series and is the answer not in the manual?

Questions and answers

Star Electricals Vatva
February 22, 2025

Start stop time

1 comments:
Mr. Anderson
February 22, 2025

The start-stop time for the INVT Goodrive20-EU VFD Series is not explicitly mentioned in the provided context. However, the "Pre-exciting time" (P03.25) is listed as a parameter that helps improve torque performance during startup, with a setting range of 0.000 to 10.000 seconds. If more specific start-stop time details are needed, they may be found in additional documentation.

This answer is automatically generated

Table of Contents

Save PDF