Goodrive20-EU series VFD
Function
Name
code
Run command
P00.01
channel
Max. output
P00.03
frequency
Upper limit of
P00.04
running
frequency
Detailed instruction of parameters
2: SVPWM control
Suitable in applications which do not need high
control accuracy, such as the load of fan and
pump. One VFD can drive multiple motors.
Note: Motor parameter autotuning is required
when vector mode is applied.
Select the run command channel of the VFD.
The control command of the VFD includes: start,
stop, forward/reverse rotating, jogging and fault
reset.
0: Keypad ("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REVC shifting function (P07.02=3) to
change the running direction; press RUN and
STOP/RST simultaneously in running state to
make the VFD coast to stop.
1: Terminal ("LOCAL/REMOT" flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2:Communication ("LOCAL/REMOT" on);
The running command is controlled by the upper
monitor via communication
This parameter is used to set the maximum
output frequency of the VFD. Users need to pay
attention to this parameter because it is the
foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04 – 400.00Hz
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD
which is lower than or equal to the maximum
frequency.
Setting range: P00.05 – P00.03 (max. output
frequency)
33
Function parameters
Default
Modify
value
0
50.00Hz
50.00Hz

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive20-EU VFD Series and is the answer not in the manual?

Questions and answers

Star Electricals Vatva
February 22, 2025

Start stop time

1 comments:
Mr. Anderson
February 22, 2025

The start-stop time for the INVT Goodrive20-EU VFD Series is not explicitly mentioned in the provided context. However, the "Pre-exciting time" (P03.25) is listed as a parameter that helps improve torque performance during startup, with a setting range of 0.000 to 10.000 seconds. If more specific start-stop time details are needed, they may be found in additional documentation.

This answer is automatically generated

Table of Contents

Save PDF