Control Cables - INVT Goodrive20-EU VFD Series Operation Manual

Hide thumbs Also See for Goodrive20-EU VFD Series:
Table of Contents

Advertisement

Goodrive20-EU series VFD
Note: A separate PE conductor is required if the conductivity of the cable shield is not
sufficient for the purpose.
C.3.2 Control cables
All analog control cables and the cable used for the frequency input must be shielded.
The relay cable needs the cable type with braided metallic screen.
Note: Run analog and digital signals in separate cables.
Check the insulation of the input power cable according to local regulations before connecting
to the drive.
Model
GD20-0R4G-S2-EU 1.5
GD20-0R7G-S2-EU 1.5
GD20-1R5G-S2-EU 2.5
GD20-2R2G-S2-EU 2.5
GD20-0R4G-2-EU
GD20-0R7G-2-EU
GD20-1R5G-2-EU
GD20-2R2G-2-EU
GD20-004G-2-EU
GD20-5R5G-2-EU
GD20-7R5G-2-EU
GD20-0R7G-4-EU
GD20-1R5G-4-EU
GD20-2R2G-4-EU
GD20-004G-4-EU
GD20-5R5G-4-EU
GD20-7R5G-4-EU
GD20-011G-4-EU
GD20-015G-4-EU
GD20-018G-4-EU
GD20-022G-4-EU
GD20-030G-4-EU
GD20-037G-4-EU
GD20-045G-4-EU
Recommended
2
cable size (mm
)
RST
PE
UVW
1.5
1.5
2.5
2.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
4
4
6
6
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
4
4
6
6
6
6
10
10
16
16
25
16
25
16
35
16
Connecting cable size
2
(mm
RST
P1, (+)
UVW
1 – 4
1 – 4
1 – 4
1 – 4
1 – 4
1 – 4
1 – 4
1 – 4
1-1.5
1-1.5
1-1.5
1-1.5
1.5 – 6
2.5 – 6
1.5 – 6
2.5 – 6
1.5 – 6
2.5 – 6
4 – 10
4 – 10
4 – 10
4 – 10
1-1.5
1-1.5
1-1.5
1-1.5
1-1.5
1-1.5
2.5 – 6
2.5 – 6
2.5 – 6
2.5 – 6
4 – 10
4 – 10
4 – 10
4 – 10
4 – 10
4 – 10
10 – 16
10 – 16 10 – 16
10 – 16
10 – 16 10 – 16
25 – 50
25 – 50 16 – 25
25 – 50
25 – 50 16 – 25
35 – 70
35 – 70 16 – 35
152
Peripheral options and parts
)
Terminal
screw
PE
1 – 4
M3
1 – 4
M3
1 – 4
M3
1 – 4
M3
1-1.5
M3
1-1.5
M3
2.5 – 6
M4
2.5 – 6
M4
2.5 – 6
M4
4 – 10
M5
4 – 10
M5
1-1.5
M3
1-1.5
M3
1-1.5
M3
2.5 – 6
M4
2.5 – 6
M4
4 – 10
M5
4 – 10
M5
4 – 10
M5
M5
M5
M6
M6
M8
Tightening
torque (Nm)
0.8
0.8
0.8
0.8
0.8
0.8
1.13
1.13
1.13
2.3
2.3
0.8
0.8
0.8
1.13
1.13
2.3
2.3
2.3
2.3
2.3
2.5
2.5
10

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive20-EU VFD Series and is the answer not in the manual?

Questions and answers

Star Electricals Vatva
February 22, 2025

Start stop time

1 comments:
Mr. Anderson
February 22, 2025

The start-stop time for the INVT Goodrive20-EU VFD Series is not explicitly mentioned in the provided context. However, the "Pre-exciting time" (P03.25) is listed as a parameter that helps improve torque performance during startup, with a setting range of 0.000 to 10.000 seconds. If more specific start-stop time details are needed, they may be found in additional documentation.

This answer is automatically generated

Subscribe to Our Youtube Channel

Table of Contents

Save PDF