Goodrive20-EU series VFD
Function
Name
code
Function
P00.18
restore
parameter
P01 Group Start-up and stop control
P01.00
Start mode
Starting
P01.01
frequency of
direct start-up
Hold time of
P01.02
the starting
frequency
Detailed instruction of parameters
0: No operation
1: Restore the default value
2: Clear fault records
3: Lock all function codes
Note: The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0: Start-up directly: start from the starting
frequency P01.01
1: Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2
The direction and speed will be tracked
automatically for the smoothing starting of
rotating motors. It suits the application with
reverse rotation when big load starting.
Note: This function is only available for the
VFDs≥4kW
Starting frequency of direct start-up means the
original frequency during the VFD starting. See
P01.02 for detailed information.
Setting range: 0.00 – 50.00Hz
Set a proper starting frequency to increase the
torque of the VFD during starting. During the
retention time of the starting frequency, the
output frequency of the VFD is the starting
frequency. And then, the VFD will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the VFD will stop running and keep in the
39
Function parameters
Default
Modify
value
◎
0
◎
0
◎
0.50Hz
◎
0.0s
Need help?
Do you have a question about the Goodrive20-EU VFD Series and is the answer not in the manual?
Questions and answers
Start stop time
The start-stop time for the INVT Goodrive20-EU VFD Series is not explicitly mentioned in the provided context. However, the "Pre-exciting time" (P03.25) is listed as a parameter that helps improve torque performance during startup, with a setting range of 0.000 to 10.000 seconds. If more specific start-stop time details are needed, they may be found in additional documentation.