Goodrive20-EU series VFD
Function
Name
code
Acceleration/
P01.05
deceleration
selection
Acceleration
time of the
P01.06
starting step of
S curve
Deceleration
time of the
P01.07
ending step of
S curve
P01.08 Stop selection
Detailed instruction of parameters
The changing mode of the frequency during
start-up and running.
0: Linear type
The output frequency increases or decreases
linearly.
fmax
1: S curve
The output frequency increases or decreases
progressively according to the S curve. The S
curve type is generally applied in elevators,
conveyors, and other application scenarios
where smoother start or stop is required.
Output frequency
t1
t1=P01.06; t2=P01.07
Setting rage: 0.0–50.0s
Note: Effective when P01.05 is 1
0: Decelerate to stop: after the stop command
becomes valid, the VFD decelerates to reduce
the output frequency during the set time. When
the frequency decreases to 0Hz, the VFD stops.
1: Coast to stop: after the stop command
becomes valid, the VFD ceases the output
Output frequency
T
t1
t2
t
t2
t1
t2
41
Function parameters
Default
Modify
value
0
0.1s
0.1s
0

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive20-EU VFD Series and is the answer not in the manual?

Questions and answers

Star Electricals Vatva
February 22, 2025

Start stop time

1 comments:
Mr. Anderson
February 22, 2025

The start-stop time for the INVT Goodrive20-EU VFD Series is not explicitly mentioned in the provided context. However, the "Pre-exciting time" (P03.25) is listed as a parameter that helps improve torque performance during startup, with a setting range of 0.000 to 10.000 seconds. If more specific start-stop time details are needed, they may be found in additional documentation.

This answer is automatically generated

Table of Contents

Save PDF