14.2.4 Configuring GAP with DHCP server

14.2.5 Manual allocation of addresses in the sub-nets

Building Technologies
Fire Safety
NOTICE
GAP with DHCP server on public network
Devices on the public network have incorrect IP addresses.
A GAP must only be configured on private networks with a DHCP server.
A ↑ GAP can be configured with a DHCP server. This results in a PC automatically
receiving an IP address when a connection is established to the GAP via C-
WEB/LAN.
w The ↑ 'Station' is configured as GAP.
1. Open the 'Global system configuration' > 'FS720 network configuration' >
'Ethernet sub-net' > 'Functions' elements in the tree view of the 'Network' task
card.
2. Highlight the 'Station'.
3. Check the 'DHCP server enabled' checkbox on the 'Overview' tab of the detail
editor.
a The 'Station' is configured with DHCP server.
If the 'Ethernet sub-net' is incorporated in an existing IT infrastructure, the settings
for the sub-net mask and IP address must be made manually following the IT
administrator's instruction.
IP addresses for Ethernet and ↑ router stations
IP addresses ranging from 192.168.200.0...192.168.200.255 to
192.168.255.0...192.168.255.255 are reserved in FS720 can cannot be used.