'Detection' task card
11
'Zone'
Main features and typical application
'Single, Standard':
●
↑ Single-detector dependency
●
With 'Pre-ALARM'
'Single, no pre-alarm':
●
Single-detector dependency
●
Without 'Pre-ALARM'
'Single, non-latching alarm':
●
Single-detector dependency
●
Without 'Pre-ALARM'
'Single, ALARM sub-system':
●
Single-detector dependency
●
With 'Pre-ALARM'
'Single, Exting. discharged':
●
Single-detector dependency
●
With 'Pre-ALARM'
'Single, Exting. pre-alarm':
●
Single-detector dependency
●
With 'Pre-ALARM'
'Single, Gas alarm':
●
Evaluation of gas detectors that are
connected via an input
●
Single-detector dependency
●
With 'Pre-ALARM'
'Single, Gas warning':
●
Evaluation of gas detectors that are
connected via an input
●
Single-detector dependency
●
With 'Pre-ALARM'
●
Only ↑ local alarming is activated in
'MAIN STAGE'
'Single, door holders':
●
Single-detector dependency
●
Without 'Pre-ALARM'
●
Only the local alarming is activated in
'MAIN STAGE'
148 | 412
Building Technologies
Fire Safety
The following table shows the properties of the templates along with the event
category and the event text of the message that is generated with an alarm.
Typical event category
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------General autom. Fire
ALARM'
' ------General autom. Fire ALARM' 'Autom. FIRE ALARM'
' ------Autom. Fire ALARM,
programmable'
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------Exting. discharged
(Aut. Fire AL.)'
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------Exting. pre-alarm
(Aut. Fire AL.)'
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
–
' --Pre-ALARM, fire'
●
'MAIN STAGE':
–
' ------General autom. Fire
ALARM'
' ------General autom. Fire ALARM' 'ALARM door holders'
Event text
1
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'Autom. FIRE ALARM'
'Autom. FIRE ALARM'
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'ALARM sub-system'
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'Exting. discharged'
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'Exting. pre-alarm'
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'Gas ALARM'
●
'PRE-STAGE':
–
'Pre-ALARM'
●
'MAIN STAGE':
–
'Gas warning'
A6V10210424_j_en_--
2018-08-29