12 'Control' Task Card; Creating Control Tree - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

12 'Control' task card

12.1 Creating control tree

Building Technologies
Fire Safety
Controls are configured in the 'Control' task card. The controls are combined into
the following ↑ control groups:
'Alarming control group': Controls for internal and external sounders and
remote transmission outputs for Fire and Fault.
↑ 'Fire control group': Controls for building equipment.
'Evac control group': Controls for ↑ alarm and announcement devices.
'Counter control group': Registration of fire alarms and test activities.
Each control group has one or more control elements including one or more inputs
(Causes) and one or more outputs (Effects).
You will find more information on control groups in the following chapters.
1. Select 'Control' > 'Station' in the task card.
2. Create a 'Control group' element for the 'Station'.
3. Enter customer texts.
4. Create a control element for the 'Control group'.
5. Enter customer texts.
Several elements are already created for 'Stations' with the template 'Alarming
pre-configured', e.g. 'Alarming control group' with pre-configured 'RT controls'.
See also
2 Create element [➙ 68]
'Control' task card
12
Creating control tree
175 | 412
A6V10210424_j_en_--
2018-08-29