Reducing address by 1
Gaps are produced in the address sequence when you delete, cut / paste, move,
or re-address elements throughout ↑ stations. Proceed as follows to close gaps in
the address sequence:
1. Highlight the element after the gap in the tree view.
2. Select 'Edit' > 'Change element address: -1' from the menu bar.
a Depending on the highlighted element, the following window will be
displayed:
3. Click on 'Yes'.
a The address of the element selected and all elements of the same level with
higher addresses are decreased by 1 across the system or within the parent
element, respectively.
Raising address by 1
Proceed as follows to paste an element, e.g. an additional 'Zone', to a particular
position in the address sequence:
1. Highlight the element before which you want to insert an element in the tree
view.
2. Select 'Edit' > 'Change element address: +1' from the menu bar.
a Depending on the highlighted element, the following window will be
displayed:
3. Click on 'Yes'.
a The address of the element selected and all elements of the same level
with higher addresses are increased by 1 across the system or within the
parent element, respectively.
a A gap appears in the address sequence.
4. Create a new element and enter the address that corresponds to the gap in the
detail editor.
a The new element is moved to the position of the gap.
Program operation
Re-addressing elements
A6V10210424_j_en_--
2018-08-29
6