Siemens FS720 Configuration page 296

Fire detection system
Table of Contents

Advertisement

'Operation' task card
13
Fire brigade periphery [DE]
296 | 412
Building Technologies
Fire Safety
Connecting with RS485
Figure 131: 'Assign dialog' window for creating and assigning to the RS485 interface
To create the logical FBF or FAT element and to assign it to the RS485 module
(FCA2002) element, proceed as follows:
1. Select the 'Operation' task card.
2. Highlight the 'Station' in the tree view.
3. Open the 'Assign dialog' window.
4. Select the corresponding element (FBF or FBF) in the list.
a The 'Hardware tree' is shown.
5. Highlight a 'UFP' element in 'RS485 module (FCA2002)'.
6. Click on 'Assign'.
a The element is created and assigned to the RS485 module (FCA2002).
Configuring visibility
The following ↑ visibilities can be configured:
Fire brigade operating panel FBF:
Visibility on the remote transmission control FIRE
Visibility on the extinguishing controls
Visibility:
'Site': Visibility for the entire ↑ site.
'Area': Visibility for one ↑ area within a control panel.
'Station': Visibility for one 'Station' within the site, with all areas in this
'Station'.
Fire brigade key depot FSD:
Visibility on the remote transmission control FIRE
A6V10210424_j_en_--
2018-08-29