13.9 Alarming equipment (UGA) [FR]

13.9.1 Creating the 'UGA' and 'UGA alarm zone' elements

13.9.2 Assigning UGA to the RS485 module

Building Technologies
Fire Safety
The alarming equipment (UGA) is an operating and indication unit for four alarm
zones. The unit has its own control for the ↑ alarm devices by alarm zone and its
own degraded mode behavior. The alarming equipment is linked to the control
panel via an RS485 interface. Up to four alarm zones can be configured for the
alarming equipment.
Configuring alarming equipment (UGA)
You will find additional information about the individual steps on the specified
pages.
1. Create the 'UGA' and 'UGA alarm zone' elements. Link [➙ 303]
2. Assign the 'UGA' element to the RS485 module. Link [➙ 303]
3. Configure the ↑ visibility. Link [➙ 304]
4. Configure the UGA master-slave principle. Link [➙ 304]
1. Select 'Operation' > 'Station' in the task card.
2. Create the 'UGA' element for the 'Station'. Link [➙ 68]
3. Create the 'UGA alarm zone' element for 'UGA'.
Figure 137: Assigning 'UGA' element
w In 'Hardware tree' the 'RS485 module (FCA2002)' element is available.
1. Select the 'Operation' task card.
2. Highlight the 'UGA' element in the tree view.
3. In the menu bar, click on 'Assign'.
a The 'Assign dialog' window opens.
4. Select 'UGA' at the left in the window.
a At the right in the window, the 'Hardware tree' is displayed.
5. Open the RS485 module and select a 'UFP' element.
6. Click on 'Assign'.
a 'UFP' is assigned to 'UGA'.
'Operation' task card
Alarming equipment (UGA) [FR]
A6V10210424_j_en_--
13
303 | 412
2018-08-29