16
Configuring flooding zone control
Designation
Preset function type: 'External equipment'
'Ventilator system'
Template ID: '9...'
'Activated 'Release
actuator' until reset'
Template ID: '29...'
'Pre-activated'
Template ID: '18...'
'Automatic release
activated'
Template ID: '2...'
'Manual release activated'
Template ID: '3...'
'External release activated'
Template ID: '4...'
'Activated while released'
Template ID: '19...'
'Activated while emergency
abort'
Template ID: '20...'
'Activated while autom.
blocked'
Template ID: '21...'
'Activated while manual
only'
Template ID: '32...'
'Activated while man.
blocked'
Template ID: '22...'
'Activated while mech.
blocked'
Template ID: '23...'
'Activated while reserve
cyl. selected'
Template ID: '24...'
'Activated while loss of
agent'
Template ID: '25...'
'Activated while isolation'
Template ID: '26...'
374 | 412
Building Technologies
Fire Safety
Description
Function for controlling a ventilator system.
Activation state: ''Activated' phase'
Deactivation state: 'Quiet'
Function for controlling an external system which is to be activated if the flooding
zone is in the phases between the ''Release actuator' phase' and 'Quiet' states.
Activation state: ''Release actuator' phase'
Deactivation state: 'Quiet
Example of use: The function can be used, for example, to configure a fail-safe
'Emergency hold' valve. To do this, the function type in the 'Overview' tab must be
set to 'Actuator/valve'. In addition, the error behavior in the 'Details' tab must be
amended to 'Activate but don't release'.
Function for activating an external system if the flooding zone is in a certain state.
The activation state in question is included in the name of the function. The
function is deactivated if the flooding zone leaves the activation state in question
again.
Activation state: Depending on the function selected, the state is included in the
name and can be obtained from the 'Overview' tab under 'Activation state'.
Deactivation: The flooding zone leaves the activation state
A6V10210424_j_en_--