Configuring Remote Access Via Crsp - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

'Network' task card
14
Network configuration

14.2.9 Configuring remote access via cRSP

320 | 412
Building Technologies
Fire Safety
4. In 'Secondary GAP', create a 'Route' element and enter the following values.
'Destination address': Sub-net of management station B – 10.169.30.0
'Netmask': 255.255.255.0
'Gateway': Address of 'Security module (firewall)' B – 192.168.100.11
5. In 'Ethernet sub-net', create two 'Route' elements.
6. Enter the following values in the first Route' element. Link [➙ 317]
'Destination address': Sub-net of management station A – 10.169.29.0
'Netmask': 255.255.255.0
'Gateway': Address of 'GAP' – 192.168.100.1
7. Enter the following values in the second Route' element:
'Destination address': Sub-net of management station B – 10.169.30.0
'Netmask': 255.255.255.0
'Gateway': Address of 'Secondary GAP' – 192.168.100.2
You will find more information about remote access with two ↑ GAPs in document
A6V10210362. See chapter 'Applicable documents'.
See also
2 Applicable documents [➙ 13]
To configure remote access via the 'common Remote Service Platform' (cRSP)
remote maintenance platform, you must request the following values from your
cRSP contact:
'Destination address'
'Netmask'
↑ 'Gateway'
You will find more information about remote access via cRSP in document
A6V10210362. See chapter 'Applicable documents'.
A6V10210424_j_en_--
2018-08-29