3.4 SICAM FSI Mounting

3.4

SICAM FSI Mounting

SICAM FSI B-Sensor Mounting Methods

3.4.1
You can mount SICAM FSI B-Sensor on the MV overhead line with one of the following tools:
Hot stick with shotgun
Hot stick with shotgun is used when the overhead line is accessible up to 4 m
Hot stick (telescopic) with device adaptor
Hot stick (telescopic) is used when the overhead line is accessible up to 12 m
For more information about SICAM FSI B-Sensor commissioning, refer to
Commissioning.
NOTE
i
i
SICAM FSI must be mounted at a distance of 2 m from any pole insulator, jumpers or any live switchgears.

Mounting SICAM FSI using Hot Stick with Shotgun

3.4.2
To mount the device on the MV overhead line with hot stick with shotgun, proceed as follows:
!
DANGER
Warning due to live voltage when mounting the device.
Non-observance of the following measures leads to death or serious injury.
Mounting the device or replacing the device must be carried out by trained personnel (see preface)
²
and must observe the safety requirements and precautions.
Before mounting the device, ensure that you wear safety helmet, gloves and boots. It is recommended
²
to use sunshields while working in bright sunny environment.
Siemens recommends using the hot stick with shotgun (Make: Ritz, Cat.No. RC403-0295 or equiv-
²
alent) with a minimum isolation of 125 kV AC. Follow safety measures and recommended mainte-
nance procedures as per the hot stick with shotgun supplier.
Ensure that the hot stick is dry and clean from dirt before mounting or unmounting the device on
²
the MV overhead line.
Do not mount and unmount the device from the MV overhead line if the weather is wet, if it is
²
raining, if there is a fog, or if snow is falling.
Do not rest or hang hot stick with shotgun with device unattended on the MV overhead line.
²
26
3.5.1 SICAM FSI V2.0 B-Sensor
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023