12.6.5 Properties of the assigned effects

Building Technologies
Fire Safety
'Overview' tab
'Main damper' ('Fire damper control' only)
If the checkbox is checked, the damper is the main damper. The state of the
control/ventilation zone is set to 'closed' if the main damper is 'closed'.
'Timeout 'close''
Defines the time within which the 'closed' state must be confirmed once the control
has activated the output.
'Timeout 'open''
Defines the time within which the 'open' state must be confirmed once the control
has activated the output.
Cascading of damper controls
You can assign the 'Effects' element to another damper control. Effect elements
with a reference to another damper control can also be defined as the 'Main
damper'.
'BACnet object name'
Customer-specific object name for the BACnet object. The 'BACnet object name'
can be selected in accordance with the project-specific naming system for the
relevant BACnet project.
'Control' task card
12
Damper control group
239 | 412
A6V10210424_j_en_--
2018-08-29