Action' Elements - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

Extinguishing
16
Configuring the extinguishing terminal

16.7.2 'Action' elements

Designation
'Reset warning panel'
'LED test'
'Toggle main/reserve
cylinder bank (local sector
only)'
'Toggle external equipment
mode'
'Toggle alarm device mode' Button switches between the operation modes of the alarm devices in the flooding
'Toggle device supervision
mode'
Parameters
'Access level'
388 | 412
Building Technologies
Fire Safety
'Extinguishing terminal' – 'Keys' – 'Action' elements
The table below describes the configurable effects when the assigned button on
the extinguishing terminal is pressed. An 'Action' element represents a cause in
each case.
Description
Button resets the 'Illuminated warning panel'.
Prerequisite: The 'Illuminated warning panel' is in the 'Illuminated warning panel
resettable' state.
Button activates the 'LED test'. All of the visible lights on the extinguishing
terminal should light up when the button is pressed. Defective lights can be
identified in this way.
Button switches between the main extinguishing agent cylinders and the reserve
extinguishing agent cylinders.
Button switches between the different operation modes of the external equipment.
The button can, for example, switch between the 'On' and Off' modes of the
external equipment.
zone.
The button globally disables monitoring for the following error messages by the
devices:
'Loss of agent'
'Incorrect position'
The isolation prevents the activation of the ↑ intervention concept (IC) of the fire
control panel if necessary.
'Action' elements – parameters in the 'Overview' tab
The table below describes the parameters in the 'Overview' tab for a 'Action'
element:
Value
'1'
'2.2'
Description
Defines the access level required to
perform the function of the button.
A6V10210424_j_en_--
2018-08-29