'Hardware' task card
10
'Station'
118 | 412
Building Technologies
Fire Safety
Configuring intervention concept
Figure 25: Detail editor with settings for the intervention concept
1. Select the 'Hardware' task card.
2. Highlight a ↑ 'Station' in the tree view.
3. Select the 'Intervention' tab in the detail editor and set the properties you want.
Immediate intervention
The following can be set for immediate intervention:
Separately for ↑ 'Manned operation' and ↑ 'Unmanned operation':
'Disabled'
'Delayed intervention'
'Global intervention only'
'Local intervention only'
Time t1 for (intervention) attendance check:
A new event must be acknowledged within this period, otherwise the
intervention concept switches to ↑ global alarming.
↑ Alarming equipment:
'RT Fire', 'RT Fault', 'RT 1' - 'RT 8', 'Internal sounder'
Service intervention
The following can be set for service intervention:
Separately for 'Manned operation' and 'Unmanned operation':
'Disabled'
'Delayed intervention'
'Direct intervention'
Time for service intervention ts:
The cause of an event must be remedied within this time period, otherwise the
intervention concept activates the service intervention alarming equipment.
Alarming equipment:
'RT Fire', 'RT Fault', 'RT 1' - 'RT 8', 'Internal sounder'