11.2.3 Alarm organization mode

11.2.4 Switching times for 'Unmanned operation'

11.3 'Section'

11.4 'Zone'

11.4.1 'Automatic zone'

Building Technologies
Fire Safety
The 'Alarm organization mode' setting determines which statuses and functions,
e.g., switchovers and indicators, of the ↑ alarm organization are used in this 'Area'.
The following can be set:
'Always manned (no messages/no LED/no switching fct.)'
'Always unmanned (no messages/no LED/no switching fct.)'
'Manned/unmanned (with messages/with LED/with switching fct.)'
Figure 48: Detail editor with settings for alarm organization mode
The time at which ↑ alarm organization automatically switches over to 'Unmanned
operation' can be specified. This is required if, for example, the alarm organization
is manually switched back to 'Unmanned operation' after being automatically
switched over to 'Manned operation'.
Four times can be entered in the 'Overview' tab.
Figure 49: Detail editor with switching times for 'Unmanned operation'
The level ↑ 'Section' is used for the zoning of 'Zones' and has no functions of its
own. In one element 'Section', for example, all 'Zones' can be combined on one
building floor. Doing so facilitates the operation.
The various 'Zone' types are described in the following chapters.
↑ Automatic fire detectors are evaluated in the 'Automatic zone'. The 'Zone' can
however also be configured for inputs or collective detector lines.
You can select between a variety of different templates that are pre-configured for
various applications for the creation of a 'Automatic zone'.
'Detection' task card
11
'Section'
147 | 412
A6V10210424_j_en_--
2018-08-29