Siemens FS720 Configuration page 372

Fire detection system
Table of Contents

Advertisement

Extinguishing
16
Configuring flooding zone control
Designation
Preset function type: 'Actuator/valve'
'Actuator/valve main/res.
cyl. bank'
Template ID: '14...'
'Actuator/valve main
cylinder'
Template ID: '12...'
'Actuator/valve reserve
cylinder'
Template ID: '13...'
'Pilot valve main/res. cyl.
bank'
Template ID: '15...'
'Pilot valve main cylinder
bank'
Template ID: '16...'
'Pilot valve reserve cylinder
bank'
Template ID: '17...'
'Emergency hold valve'
Template ID: '11...'
372 | 412
Building Technologies
Fire Safety
'Effects functions of the 'Function' element type
The table below describes the 'Effects' functions, which can also be created
manually.
Description
Function for triggering the opening of the pneumatic shut-off valves on the main
or reserve extinguishing agent cylinders.
Information: The actuator for the valve can only ever be either opened or closed
with this function. Whether the actuator should be opened or closed depends on
the technical design of the opening mechanism. Furthermore, the function is only
intended for extinguishing systems with a central cylinder battery.
Information: If necessary, the element can be deleted and created again.
Activation state: ''Release actuator' phase'
Deactivation: After the time set under 'Activation duration' has elapsed
Function for triggering the opening of the pneumatic shut-off valves on the main
extinguishing agent cylinders.
Information: The function can only open the shut-off valves but not close them
again.
Activation state: ''Release actuator' phase, main cylinder bank'
Deactivation: After the time set under 'Activation duration' has elapsed
Function for triggering the opening of the pneumatic shut-off valves on the
reserve extinguishing agent cylinders.
Information: The function can only open the shut-off valves but not close them
again.
Activation state: ''Release actuator' phase, reserve cylinder bank'
Deactivation: After the time set under 'Activation duration' has elapsed
Function for opening the shut-off valve for the control air supply of the main
extinguishing agent cylinder or the reserve extinguishing agent cylinder.
Activation state: ''Activated' phase'
Deactivation: After the time set under 'Activation duration' has elapsed
Function for opening the shut-off valve for the control air supply of the main
extinguishing agent cylinder.
Activation state: ''Activated' phase', main cylinder bank'
Deactivation: After the time set under 'Activation duration' has elapsed
Function for opening the shut-off valve for the control air supply of the reserve
extinguishing agent cylinder.
Activation state: ''Activated' phase', reserve cylinder bank
Deactivation: After the time set under 'Activation duration' has elapsed
Function for activating the central shut-off valve in the control air in-feed for the
opening valves on the extinguishing agent cylinders. An 'Emergency hold'
function can be realized through targeted opening and closing of the shut-off
valve.
Activation state: 'Emergency hold active'
Deactivation: 'When leaving activation state'
A6V10210424_j_en_--
2018-08-29