Ethernet Switch (Modular) Fn2012 - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

10.7 Ethernet switch (modular) FN2012

Building Technologies
Fire Safety
Configuring an Ethernet switch (modular) FN2012
w The Ethernet switch (modular) FN2012 is integrated into the station and is
connected to it via a ribbon cable.
w The current configuration is loaded to the PC. You will find more information on
this in chapter 'Loading configuration from the station to the PC [➙ 108]'.
1. Create an 'Ethernet switch (modular, FN2012)' element in the 'Hardware' task
card for the station that the FN2012 is connected to.
Alternatively: Import all new devices onto the station and then load the
configuration to the PC.
2. Configure the IP address for the FN2012.
3. Configure the redundancy management of the Ethernet ring if you configure an
Ethernet network with several elements of the type 'Ethernet switch (modular,
FN2012)'. Link [➙ 324]
4. Configure the local ports of the FN2012.
Configuring the IP address
w An 'Ethernet switch (modular, FN2012)' element is created within a station in
the 'Hardware' task card.
1. Open the 'Network' task card.
2. Highlight the following element: 'Global system configuration' > 'FS720 network
configuration' > 'Ethernet sub-net' > 'Connections' > 'Station with the FN2012'
3. In the 'Overview' tab, enter the IP address of the FN2012 under 'IP address
network switch'.
Resetting the network configuration
If the 'Reset network configuration' command is executed in the 'Network' menu,
the IP address of the FN2012-A1 is set to 192.168.99.x. The network mask is set
to 255.255.248.0.
'Hardware' task card
Ethernet switch (modular) FN2012
A6V10210424_j_en_--
10
137 | 412
2018-08-29