Extinguishing
16
Configuring an extinguishing reporting zone
Main features and typical application Typical event category
●
Monitors the trigger signal for
extinguishing in the relevant
flooding zone
●
When extinguishing is triggered,
an alarm is triggered.
●
Isolation of the flooding zone
●
Fault monitoring in the flooding
zone
Main features and typical application Typical event category
●
Monitors the trigger signal for
extinguishing in the relevant
flooding zone
●
When extinguishing is triggered,
an alarm is triggered.
●
Isolation of the flooding zone
●
Fault monitoring in the flooding
zone
380 | 412
Building Technologies
Fire Safety
'Extinguishing reporting zone' – 'Reporting 'pre-alarm'' – properties of
the template
' ----Pre-ALARM, extinguishing
released'
NOTICE! This event has an
individual AVC concept which
bridges the global AVC settings
upon occurrence.
' --Other isolation'
' --Other fault'
Text that is shown on the display of the Person Machine Interface when the event
1
occurs.
'Extinguishing reporting zone' – 'Reporting 'alarm'' – properties of the
template
' ------Exting. discharged (Aut. Fire
AL.)'
NOTICE! This event has an
individual AVC concept which
bridges the global AVC settings
upon occurrence.
' --Other isolation'
' --Other fault'
Text that is shown on the display of the Person Machine Interface when the event
1
occurs.
Creating and configuring the 'Extinguishing reporting zone'
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w An 'Section' element is created in the 'Detection tree'.
1. Under the 'Section' element, create an 'Extinguishing reporting zone' element
with the required template.
2. Enter the required customer text in the 'Overview' tab.
Event text
1
'Exting. released'
'Exting.sector OFF'
'Extng.sector fault'
Event text
1
'Exting. released'
'Exting.sector OFF'
'Extng.sector fault'
A6V10210424_j_en_--