Configuring The Extinguishing Terminal - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

Extinguishing
16

Configuring the extinguishing terminal

16.7 Configuring the extinguishing terminal
382 | 412
Building Technologies
Fire Safety
The 'Extinguishing terminal' element contains all configurable indication elements
and operating elements of an extinguishing terminal.
Creating and configuring an 'Extinguishing terminal' element
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w A 'Station' element is created.
1. Create an 'Extinguishing terminal' element for each integrated or remote
extinguishing terminal in the 'Operation tree' within the 'Station'.
a The tool creates an 'Extinguishing terminal' element with configurable 'LED'
and 'Keys' elements.
2. Set the required customer text and the parameters of the 'Extinguishing
terminal' element in the 'Overview' tab.
3. Configure every 'Extinguishing terminal' element in the 'Details' tab.
4. Assign the corresponding 'Default XTO2001' element or 'Optional XTO2001'
element to each 'Extinguishing terminal' element with 'Assign' within the
extinguishing card in the 'Hardware tree'. Information: The required number of
'Optional XTO2001' elements must be created in 'Hardware tree' so that these
are visible in 'Assign dialog'.
5. Set the customer texts for the required LED lights in the 'Overview' tab.
A6V10210424_j_en_--
2018-08-29