Siemens FS720 Configuration page 250

Fire detection system
Table of Contents

Advertisement

'Control' task card
12
Sounder line via input/output module FDCIO223
250 | 412
Building Technologies
Fire Safety
4. In the toolbar, click on 'Assign'.
a The 'New effect dialog' window opens.
a The 'Hardware tree' is depicted at the right of the window. The elements
that can be assigned are highlighted.
5. Open the FDCIO223 input/output module and select
'Collective/input/sounder/output'.
6. Click on 'Assign'.
a 'Collective/input/sounder/output' is assigned to 'Effects'.
Setting the properties of the 'Sounder' line
1. Highlight the assigned 'Sounder' line in the tree view.
2. Set the properties you want in the detail editor.
The following properties can be set in the 'Overview' tab:
Figure 80: Settings in the detail editor of the sounder line
'Enabled':
The two settings 'Enabled' specify whether a time-out is used for the activation of
the control. The time-out can be set separately for 'Manned operation' and
'Unmanned operation'.
'Activation timeout 'manned'':
This setting specifies the duration of the time-out in 'Manned operation'. The time-
out is started when the control is activated. After the expiration of the set time, the
sounder is deactivated automatically.
A6V10210424_j_en_--
2018-08-29